|
To be acceptable for fumigation, an empty
container must be in sound (good) conditions
with no holes or other opening in nay part of
the walls, floor or ceiling that cannot be
sealed. Therefore before attempting to fumigate
a container a careful inspection should be made.
A certain amount of sealing may be necessary if
ventilation or drainage apertures are present
and any cracks or holes caused by accidental
damage must also be sealed with masking tape or
some other suitable material. The door must be
closed tightly against the rubber gasket. Badly
fitting doors may need to be taped over around
the edges and where the door meets. Badly
damaged containers should be fumigated under
tarpaulin.
Preloading preparations can eliminate may
potential leaks. The container may be lined with
minimum 6-mil polyethylene sheeting. Even if
some leaks develop due to mechanical damage
during loading, less leakage will result when a
lining is used.


The container must not be closely stacked with
cargo. Sufficient space must be left for
distribution of the gas over, under and through
the load. The container should not be loaded
with more than two thirds of its capacity,
unless otherwise specified in the treatment
schedule. Commodities that have no penetration
or circulation problem can be allowed a load
limit of 80% of the space. The commodities
should be more than 60cm (2ft) from the ceiling.
In order to provide sufficient space for air
movement, part of the load can be placed under
the container (if on chasis) or stacked around
the container (if under tarp).
Preloaded containers with non- permeable cargo,
that is, contents wrapped or packaged with non-
permeable materials, will need to be unloaded
from the container and the contents opened for
fumigation. Cello phone, plastic, polyethylene,
vinyl, waterproof paper, waxed and laminated
materials and even tight wooden packing cases
are relatively gas tight. Contents that are
difficult to penetrate are also difficult to
aerate after treatment.

An axial type fan with a capacity of at least
71m3/ min (2500 CFM) must be used the circulate
the fumigant. The fan must be placed at the open
door and positioned to blow over the floor
towards the back of the container. The fan
should run 15-20 minutes after the introduction
at the fumigant. If several containers are
fumigated under the same sheet, additional fans
are necessary. For every container under the
sheet, a fan of 71m3/min (2500 CFM) capacity
should be used.

The gas may be introduced through a gas
injection nozzle (or application points) in the
side of the containers. The containers operated
by some companies are provided with application
points at roof level, one point for a 20 ft
container and two points for a 40 ft container.
The gas may also be introduced through a tube or
nozzles inserted at the door overlap (gasket) on
top where the doors meet.
If the container has not been fitted with
application points, it may be possible to drill
a small hole in the wall or at the pivet. To
accord with Customs requirements the hole should
not exceed 3 mm in diameter.
If the fumigant is applied from cans or
cylinders, the cans should be warmed in hot
water for a few minutes before use to aid the
rapid delivery of the contents and they
subsequent vaporization. When gas are released
from cylinders, warming is through the
volatilizes.

Containers should be aerated thoroughly before
being released for unloading or loading. The
doors should remain closed pending
loading/unloading to prevent possible
reinfestation. |